BACKGROUND
Due to unexpectedly high vibration levels in a newly commissioned chilled water pump located at Tampines Mall, Alstern Technologies Singapore Pte Ltd engaged SPM to conduct a comprehensive vibration analysis. This analysis involved on-site testing by SPM engineer, including run-up and coast-down tests. The resulting report provides a detailed assessment of the pump’s vibrational characteristics and offers recommendations to mitigate the observed high vibration and ensure optimal operational performance and extended service life. Data acquisition was performed using industry-standard portable instrumentation.
TOOLS
The following instruments were used to perform the vibration and bearing condition measurement:
- Leonova Diamond (HD Analysis, VIB/SPM HD Expert)
- Condmaster Ruby Software
- accelerometer (AC115-M12D)
TEST CONDUCTED
- Vibration data were collected using Leonova Diamond on site by SPM Service Engineer
- Vibration data were imported to Condmaster Software for analysis.
MEASUREMENT POINT LAYOUT
- VIBRATION SEVERITY & CRITERIA LIMIT
ISO 10816 STANDARD
Vibration measurement is a technique commonly used to identify and assess the magnitude of vibration in machinery or mechanical systems. It is an important technique in predictive maintenance and can help diagnose faults and abnormalities such as Imbalance, Misalignment, Mechanical Looseness, Bearing Faults, Gear Problems, Resonance and Electrical faults especially in the early stages. By measuring and analyzing vibration levels, maintenance professionals can make informed decisions about repairs and replacements, leading to cost savings and reduced downtime.
The root mean square (RMS) value of vibration velocity, measured in mm/s (or inch/s), is utilized as a criterion for categorizing machines into three distinct classifications: “Good”, “Unsatisfactory” or “Deteriorated”.
ISO 10816 Part 3 Standards classifies industrial machinery in following groups:
Group 1: Large machines with rated power above 300 kW and not more than 50 MW.
Group 2: Medium-sized machines with rated power above 15 kW up to and including 300 kw.
Group 3: Machines with rated power above 15 kw with external driver and radial and axial mixed flow.
Group 4: Machines with rated power above 15 kw with integral driver and radial and axial mixed flow.
SUMMARY AND RECOMMENDATION
Recommendations
The following recommendations are made to mitigate the identified vibration problems:
- Addressing System Resonance
• Operational Adjustments: Avoid operating the pump at speeds that excite the resonant frequencies (approximately 70% and 90% of the rated speed, based on the observed resonance frequencies). A detailed analysis of the pump’s operating speed versus vibration amplitude should be conducted to precisely determine the problematic speed ranges. - Structural Reinforcement: If avoiding the resonant speed ranges is not feasible, structural reinforcement of the motor base frame is recommended. This may involve adding stiffeners, increasing the base’s mass, or other modifications to shift the natural frequencies away from the operating range.
- Addressing Shaft Imbalance
• Source Identification: Conduct a motor solo run test to isolate whether the imbalance originates from the motor or the pump. This involves disconnecting the pump from the motor and running the motor independently to measure its vibration levels.
• Balancing: If the imbalance is confirmed, field balancing of the rotor (either motor or pump, depending on the source identified) is necessary. This involves adding or removing weight at specific locations on the rotor to correct the imbalance.